| Sign In | Join Free | My benadorassociates.com |
|
Brand Name : XINGJIN
Delivery Time : 15-20days
Model Number : J-SAP-JBF4121A
Alarm current : ≤1mA (24V)
Explosion-proof mark : Ex ib IIC T6 Gb
Place of Origin : Guangzhou,China
MOQ : 100 set system
Packaging Details : Wooden Box Or Plywood Outer Box With Bubble Bag Or Paper
Working voltage : DC 18-28V
Dimensions of the shape : 90* 90*52mm
Payment Terms : T/T,L/C
Supply Ability : 300000 sets per month
Price : USD3-4/pc
Certification : CCC;GB/T 3836.1-2021;GB/T 3836.4-2021;GB 19880-2005
Monitor current : ≤0.3mA (24V)
Encoding method : Electronic encoder encoding
This explosion-proof manual fire call point is a manual alarm station specially designed for hazardous areas with flammable gases. By pressing the operation panel, it sends a fire signal to the fire alarm control panel. The product adopts an intrinsically safe explosion-proof design with Ex ib IIC T6 Gb marking, suitable for Zone 1 and Zone 2 hazardous areas containing IIA, IIB, and IIC class T1–T6 combustible gases. Built with a microprocessor and non-polarized two-bus technology, the transmission distance can reach up to 1000 meters. It can seamlessly connect with controllers, providing reliable manual fire alarm functionality for chemical plants, petroleum facilities, gas stations, and similar locations.
This product is widely used in the following commercial and industrial premises:
The product has passed strict inspection by the National Center for Quality Supervision and Testing of Explosion-Proof Electrical Products (CQST) with Ex ib IIC T6 Gb marking, suitable for explosive environments containing IIA, IIB, and IIC class T1–T6 combustible gases. The intrinsically safe design requires connection with a safety barrier, ensuring that even in the event of a failure in hazardous areas, it will not generate sparks or high temperatures sufficient to ignite explosive gases, providing reliable safety assurance for high-risk places such as petrochemical facilities.
Built with a high-performance microprocessor and SMT surface mount technology, the components have good consistency and high reliability. Intelligent algorithms accurately identify button activation status, avoiding false alarms. Electronic addressing allows on-site programming with a dedicated encoder, with an addressing range of 1–200 points, facilitating engineering commissioning and later maintenance.
Adopting non-polarized two-bus technology, the standby current is ≤0.3mA and alarm current ≤1mA, achieving extremely low power consumption. The communication distance can reach up to 1000 meters, supporting coverage of large industrial areas. The non-polarized bus design eliminates the need for polarity distinction during wiring, significantly reducing installation difficulty and labor costs.
The button body adopts a plug-in structure design. During installation, simply insert the encoded body into the base and secure with self-tapping screws. Disassembly and maintenance are equally simple and quick. The operation panel must be reset with a special key after being pressed, preventing unauthorized operation and ensuring system management security.
The panel features a red fire alarm indicator light that flashes momentarily in normal monitoring status and becomes steady red when activated. The status display is clear and intuitive. Even in dimly lit industrial environments, the working status and alarm status of the button can be easily identified.
This product is an intrinsically safe explosion-proof device. The following requirements must be strictly observed during use:
| Parameter | Specification |
|---|---|
| Operating Voltage | DC 18–28V (via safety barrier) |
| Standby Current | ≤0.3mA (24V) |
| Alarm Current | ≤1mA (24V) |
| Explosion-Proof Marking | Ex ib IIC T6 Gb |
| Addressing Method | Electronic encoder |
| Addressing Range | 1–200 |
| Indicator Light | Standby: Flashing momentarily; Alarm: Steady red |
| Wiring Method | Two-bus, non-polarized |
| Transmission Distance | ≤1000m (conductor cross-section ≥1.0mm²) |
| Operating Temperature | -10℃ to +55℃ |
| Storage Temperature | -30℃ to +75℃ |
| Relative Humidity | ≤95% (40±2℃) |
| Dimensions | 90mm × 90mm × 52mm |
| Weight | 170g |
| Mounting Hole Distance | 60mm (compatible with 50mm) |
| Recommended Wire | RVS 2×1.5mm² twisted pair |
|
|
Explosion-Proof Intrinsically Safe Manual Fire Alarm Button with Non-Polarized Two-Bus for Hazardous Area Fire Alarm System Images |