Brand Name : XINGJIN

Model Number : CM1004

Certification : CCC,CAC,ROHS

Place of Origin : Guangzhou,China

MOQ : 20 set system

Price : negotiation

Payment Terms : T/T, L/C

Supply Ability : 30000set/month

Delivery Time : 15-20days

Packaging Details : Plywood outer box with bubble bag or paper

Color : Grey/Red

Mains supply : 90 to 270VAC, 50Hz/60Hz

Battery charge current : 0.7A maximum

Composition : Converntional Control Panel/Light/Button/Alarm/Bell/Detector

Weight : 12.38kg

IP Rating : ip68

Light intensity : 135cd

Contact Now

Complete fire alarm system


Introduction:​
This fire alarm system features a modular design, integrating four-zone fire detection, automatic fire extinguishing control, and audible and visual alarms. The system's core control panel is EN54 certified, supports smoke and heat detectors, and is equipped with a 28VDC solenoid valve drive output for activation of various gas fire extinguishing devices. Dual power supply ensures continuous operation for at least 24 hours after a main power outage, meeting the fire protection needs of commercial and industrial sites.
System composition:
The system includes a control unit, manual call point, alarm bell and siren, and emergency broadcast module. All components have passed environmental compatibility testing and are designed to operate stably in high-temperature and high-humidity environments. Intelligent diagnostics monitor line status in real time, effectively preventing false alarms and missed alarms.
Easy-to-install fire damper interfaces allow for quick integration into existing ventilation systems.
Electrical specifications:

ITEMELECTRICAL RATINGCOMMENT
Size383mm W x 295mm H x 87mm D metal enclosure
Weight5kg
Mains supply90 to 270VAC, 50Hz/60Hz
Mains supply fuse3 Amp ( F3A L250V)Replace only with similar type
Power supply rating3 Amps total including battery charge 28V +/- 2V
Maximum ripple voltage≤200 millivolts
Battery typeTwo 12 Volt sealed lead acid in series.7Ah maximum
Battery charge voltage27.6VDC nominal
Battery charge current0.7A maximum
Current draw in mains fail condition0.095 AmpsWith buzzer sounding
Current draw in second stage alarm0.235AmpsTwo zones in fire(470 ohm in circuit)
Current draw in post discharge condition0.310Ampssolenoid outputs active
Maximum current draw from batteries3AmpsWith main power disconnected
NAC outputs(sounder & bell circuit)26 to 28V DC Fused at 500mA with electronic fuse1.2Amp total load over all circuits
Fault relay contact rating2A /30VDC maximum for eachVolt free changeover contact
Fire relay contact rating2A /30VDC maximum for eachVolt free changeover contact
First stage contact rating2A /30VDC maximum for eachVolt free changeover contact
Second stage contact rating2A /30VDC maximum for eachVolt free changeover contact
Extract contact rating2A /30VDC maximum for eachVolt free changeover contact
Zone quiescent current4mA maximum
Terminal capacity0.5mm2 to 2.5mm2 solid or stranded wire
Number of detectors per zone≤30 PCS conventional detectors
Number of sounders per circuitDependent on type and current consumption
Detection circuit end of line4K7±5% 1/2 Watt resistor3K-5.6K 1/2W
Monitored input end of line4K7±5% 1/2 Watt resistor3K-5.6K 1/2W
Sounder circuit end of line10K±5% 1/2 Watt resistor6.8K-20K 1/2W
Extinguishant output end of line10K±5% 1/2 Watt resistor6.8K-20K 1/2W
No. of detection circuitsFour 21 to 28V DC
No. of sounder circuitsFour 21 to 28V DC
Extinguishant release output21V to 28V DC. Maximum load 2 Amp
Extinguishant release delay timeAdjustable 0 to 75 seconds5 second steps
SIL, AL, FLT, RST inputsSwitched – min resistance 0 ohms, max 1k ohms
Detector alarm threshold270 ohms to 1K ohms
Call point alarm threshold150 ohms to 1K ohms
Short circuit threshold0 ohms to 130 ohms
Status unit/Ancillary board connectionTwo wire RS485 connection with electronic fuse.Max. of 32 units-RS485 data cable

Fire Alarm System Packaging and Shipping
Packaging:
fire suppression systems will be carefully packaged for safe shipping and handling. The packaging will include the following materials: heavy-duty cardboard boxes, bubble wrap, protective foam padding,.
Shipping:
All shipments will be made using a reliable and trustworthy courier service to ensure prompt and safe delivery. Customers will receive a tracking number via email after their order has been shipped.
Special Handling Instructions:
If you require any special handling instructions for your shipment, please contact us at least 24 hours before your order is shipped. We will do our best to accommodate your requests.
Thank you for choosing our fire alarm system. We hope it provides you with the peace of mind and security you need
Advanced FM200 Fire System Complete Kit with Detection and Alarm Integration


Why Choose Us​
Advanced FM200 Fire System Complete Kit with Detection and Alarm Integration

Advanced FM200 Fire System Complete Kit with Detection and Alarm Integration


Quality Advanced FM200 Fire System Complete Kit with Detection and Alarm Integration for sale

Advanced FM200 Fire System Complete Kit with Detection and Alarm Integration Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Guangzhou Xingjin Fire Equipment Co.,Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)